====== Checklist: Test reports of airtightness measurements ====== Is the air tightness measurement protocol complete? This can be easily confirmed using this checklist: * Is all general information included? * Tester: name, address and signature * Object * Date of test * Device * Measurement standard (norm) * Inside and outdoor temperatures * Wind velocity * Flow coefficient Cenv * Leakage coefficient CL * Is the airtightness measurement performed in accordance with ISO 9972 (Method 1)? * Is room-by-room calculation of the air volume of the building included? Is the calculation correct? * Has the installation location of the fan been documented? * Has temporary sealing of the building envelope been recorded (sealing of outdoor air and exhaust air ducts at least)? * Has a series of measurements at positive pressure AND negative pressure been performed? * For each series of measurements, were 5 measuring points used at different pressure differences (highest value ± 50 Pa at least)? * Is the flow exponent "n" between 0.5 and 1.0 (otherwise indicates measurement error due to a change in the envelope e.g. window opening)? * Is the average value of the natural pressure difference between -5 and 5 Pa (measurement of the pressure difference before and after each measurement series)? * //Note:// If the wind speed is greater than 6 m/s (21.6 km/h) OR the wind force is higher than 3 Beaufort, the stated limiting values for the pressure difference will usually be exceeded. * In general, the positive and negative pressure values n50 are relatively close to each other. If there are significant differences between the two results, a plausible explanation should be given in the measurement report. **Recommendation:** leakage detection at negative pressure should be carried out before the measurements, and any large leaks should be rectified and this should be documented. **Exception:** For the measurement of tall buildings (e.g. high-rise buildings) special boundary conditions apply. Please contact your certifier or building.certification@passiv.de {{:picopen:v1.2_checklist_test_reports_of_airtightness_measurements.pdf|Checklist: Test reports of airtightness measurements for download }} ==== See also ==== Record of an airtightness test: [[:certification:certified_passive_houses:example_documents|]] [[..:airtightness_measurement_of_high-rise_buildings_guidelines|]] [[..:..:airtight_construction|Overview of the Passipedia articles on airtightness]] Click [[..:..:guides_and_aids|here]] to go back to the Guides and Aids