Appendix A - Punctiform penetrations of thermally insulated exterior walls

Passivhaus Institut, Darmstadt

For estimating how high the additional heat loss due to fastening elements that penetrate the thermally insulated outer shell is, $\chi $-values for steel and high-grade steel anchors are provided in the following section. Two insulation thicknesses and two anchoring substrates are considered. The results are summarised Fig. A1. Here one can see the significant reduction in the $\chi $-value when high-grade steel is used instead of structural steel.

$\chi $-values for penetrations with structural steel and high-grade steel in masonry walls and reinforced concrete walls with an insulation thickness of 25 and 30 cm

In the case of structural steel which is more thermally conductive, the thermal conductivity of the anchoring substrate has a greater effect than the insulation thickness of the exterior wall. This applies in particular to the larger rod diameters. On the other hand, with stainless steel the thermal conductivity of the anchoring substrate has less influence than the insulation thickness. If thin anchor cross-sections (up to approx. 10 mm) are used, the influence of the insulation thickness and the anchoring substrate can be disregarded for both steel and high-grade steel elements. This is illustrated by the following example: a façade is attached using four steel anchors per m², each with a diameter of 6 mm. Table A1 shows the corresponding $\chi $-values and the impact on the U-value of the wall:

Exterior wallInsulation thicknessU-value of the uninterrupted wall$\chi $-value of each anchorU + ΔUIncrease in the U-value
Masonry wall30 cm0.127 W/(m²K)0.0035 W/K0.141 W/(m²K)11.1 %
Masonry wall25 cm0.151 W/(m²K)0.0040 W/K0.167 W/(m²K)10.6 %
Reinforced concrete30 cm0.129 W/(m²K)0.0037 W/K0.143 W/(m²K)11.5 %
Reinforced concrete25 cm0.153 W/(m²K)0.0042 W/K0.170 W/(m²K)11.0 %