planning:non-residential_passive_house_buildings:ph_hospitals:baseline_study_-_implementing_the_passive_house_concept_in_hospitals [2022/03/15 16:08] – [Summary] corinna.geiger@passiv.de | planning:non-residential_passive_house_buildings:ph_hospitals:baseline_study_-_implementing_the_passive_house_concept_in_hospitals [2023/02/01 09:50] (current) – yaling.hsiao@passiv.de | ||
---|---|---|---|
Line 2: | Line 2: | ||
+ | Below you find a summary of the **Baseline study - implementing the Passive House concept in hospitals**. It was conducted under behlaf of the Ministry of Economic Affairs, Energy, Transport, and Housingfor the State of Hesse. | ||
+ | **The full study can be downloaded [[https:// | ||
- | + | Note: The guide was developed | |
- | + | ||
- | Below you find a summary of the **Baseline study - implementing the Passive House concept | + | |
---- | ---- | ||
Line 22: | Line 22: | ||
When it comes to implementing the Passive House concept, a few special aspects of hospitals must be taken into consideration, | When it comes to implementing the Passive House concept, a few special aspects of hospitals must be taken into consideration, | ||
- | An analysis of guidelines shows that the use of tried and tested energy-saving technologies faces no obstacles in principle. Indeed, hygiene and energy efforts sometimes complement each other. High-quality insulation on potable water lines and optimized taps (in accordance with RKI 1) used only where water is frequently needed reduce the risk of Legionella' | + | An analysis of guidelines shows that the use of tried and tested energy-saving technologies faces no obstacles in principle. Indeed, hygiene and energy efforts sometimes complement each other. High-quality insulation on potable water lines and optimized taps (in accordance with RKI 1) used only where water is frequently needed reduce the risk of Legionella' |
- | In rooms where medical care is provided, the greatest comfort is at room temperatures between 22 and 23 °C. For patients not wearing a lot (such as when they are washed in bed), room temperatures should be higher. In addition, the wide range of energy applications depends on the type of clinic. The study [[http:// | + | In rooms where medical care is provided, the greatest comfort is at room temperatures between 22 and 23 °C. For patients not wearing a lot (such as when they are washed in bed), room temperatures should be higher. In addition, the wide range of energy applications depends on the type of clinic. The Baseline study on implementing the Passive House concept in hospitals investigates those most relevant for energy. \\ |
Often, the question is whether efforts to reduce heat demand are worthwhile if there is so much waste heat from processes within the hospital anyway. A closer analysis of processes that use low-temperature waste heat shows that the additional processes needed to recover that heat would reduce the benefits, in terms of primary energy, to just a fraction. The use of waste heat from inefficient processes and devices is a good idea and should be investigated, | Often, the question is whether efforts to reduce heat demand are worthwhile if there is so much waste heat from processes within the hospital anyway. A closer analysis of processes that use low-temperature waste heat shows that the additional processes needed to recover that heat would reduce the benefits, in terms of primary energy, to just a fraction. The use of waste heat from inefficient processes and devices is a good idea and should be investigated, | ||
Line 52: | Line 52: | ||
===== Heating ===== | ===== Heating ===== | ||
- | Hospitals are generally large, compact buildings. The study [[http:// | + | Hospitals are generally large, compact buildings. The Baseline study - implementing the Passive House concept in hospitals shows that the use of efficient technologies can, with reasonable effort, reduce heating demand to 15 kWh/(m²a) even though target indoor temperatures and air exchange rates are greater than in other buildings. \\ |
As in other Passive House buildings, good insulation means that the type of heat distribution does not matter much. Still, for various reasons, it is more practical to use surface heating systems in hospitals so that ventilation and heat run separately. Synergies can occur, for instance, when radiators are used for both heating and cooling. \\ | As in other Passive House buildings, good insulation means that the type of heat distribution does not matter much. Still, for various reasons, it is more practical to use surface heating systems in hospitals so that ventilation and heat run separately. Synergies can occur, for instance, when radiators are used for both heating and cooling. \\ | ||
Line 149: | Line 149: | ||
**[Destatis 2009]** Statistisches Bundesamt, Stand 2009 \\ | **[Destatis 2009]** Statistisches Bundesamt, Stand 2009 \\ | ||
- | **[[http:// | + | **[[http:// |
**[KRINKO 2012]** Anforderung an die Hygiene bei der Aufbereitung von Medizinprodukten, | **[KRINKO 2012]** Anforderung an die Hygiene bei der Aufbereitung von Medizinprodukten, | ||
Line 161: | Line 161: | ||
**[SIA 380-4]** SIA 380-4, Ausgabe 2006: Elektrische Energie im Hochbau, Schweizerischer Ingenieur- und Architektenverein, | **[SIA 380-4]** SIA 380-4, Ausgabe 2006: Elektrische Energie im Hochbau, Schweizerischer Ingenieur- und Architektenverein, | ||
\\ | \\ | ||
+ | |||
+ | ---- | ||
====== See also ====== | ====== See also ====== | ||
Line 167: | Line 169: | ||
[[planning: | [[planning: | ||
+ | |||
+ | Click [[planning: | ||
[[phi_publications: | [[phi_publications: | ||
Line 172: | Line 176: | ||
[[http:// | [[http:// | ||
- | [[http:// |
planning/non-residential_passive_house_buildings/ph_hospitals/baseline_study_-_implementing_the_passive_house_concept_in_hospitals.1647356921.txt.gz · Last modified: 2022/03/15 16:08 by corinna.geiger@passiv.de