User Tools

Site Tools


basics:affordability:economic_feasibility_of_passive_house_design

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
basics:affordability:economic_feasibility_of_passive_house_design [2015/07/01 10:44] – [3Cost effective deep energy renovation] kdreimanebasics:affordability:economic_feasibility_of_passive_house_design [2019/02/28 09:45] (current) cblagojevic
Line 13: Line 13:
 The energy-cost savings then can be used to finance the extra investment cost which are probably needed to get better building components to form the energy efficient building envelope: The energy-cost savings then can be used to finance the extra investment cost which are probably needed to get better building components to form the energy efficient building envelope:
   * more and better thermal insulation layer   * more and better thermal insulation layer
 +
   * windows with low U-value < 0.85 W/m²K   * windows with low U-value < 0.85 W/m²K
 +
   * ventilation system with heat recovery   * ventilation system with heat recovery
 +
   * …   * …
 To compare energy cost savings with extra investment costs both cost categories have to be re-calculated via dynamic finance calculation methods: annual expenses must be transformed to present cash value or vice versa.  In doing so the reduced energy costs and the relevant investment costs, respectively – see figure 1 for several variants of renovation a building – can be added up easily.  To compare energy cost savings with extra investment costs both cost categories have to be re-calculated via dynamic finance calculation methods: annual expenses must be transformed to present cash value or vice versa.  In doing so the reduced energy costs and the relevant investment costs, respectively – see figure 1 for several variants of renovation a building – can be added up easily. 
Line 38: Line 41:
 The Passive House buildings all have a mechanical ventilation system with heat recovery. To compare cost of LEB an exhaust air ventilation system with one fan, silencers and outside air inlets in walls was accounted for, as this is required in Germany since 2009 to provide sufficient (hygienic) continuous air change. For all other configuration features see in table in figure 2. The Passive House buildings all have a mechanical ventilation system with heat recovery. To compare cost of LEB an exhaust air ventilation system with one fan, silencers and outside air inlets in walls was accounted for, as this is required in Germany since 2009 to provide sufficient (hygienic) continuous air change. For all other configuration features see in table in figure 2.
 \\ \\
-The costs of all components relevant for energy savings are accounted for in this section. So not only building envelope components, but also building service components are included: cost of ventilation and heating system are fully accounted for. Accordingly in this section the final energy demand for the heating system including heat distribution losses and including auxiliary electricity for ventilation and heating system was used to calculate energy costs. This approach is used in PHPP9 and PHeco in general, as this allows to fully account for the real situation of the user and investor: all costs have to be accounted for and are to be compared.+The costs of all components relevant for energy savings are accounted for in this section. So not only building envelope components, but also building service components are included: cost of ventilation and heating system are fully accounted for. Accordingly in this section the **final energy** demand for the heating system **including heat distribution losses and including auxiliary electricity** for ventilation and heating system was used to calculate energy costs. This approach is used in PHPP9 and PHeco in general, as this allows to fully account for the real situation of the user and investor: all costs have to be accounted for and are to be compared.
  
  
Line 52: Line 55:
 The costs coming out of the invoicing are sorted by components and energy saving actions, see figure 3, such as:  The costs coming out of the invoicing are sorted by components and energy saving actions, see figure 3, such as: 
   * air tightness   * air tightness
 +
   * thermal insulation of cellar, bottom slab, outside wall, roof   * thermal insulation of cellar, bottom slab, outside wall, roof
 +
   * windows, entrance door, shading   * windows, entrance door, shading
 +
   * heating system   * heating system
 +
   * ventilation system   * ventilation system
 To compare the costs of several components specific cost values in €/m² were calculated. The area used is the same treated floor area, which is used in PHPP to do energy balance calculations. So cost data for investment and energy consumption can easily and directly be compared. To compare the costs of several components specific cost values in €/m² were calculated. The area used is the same treated floor area, which is used in PHPP to do energy balance calculations. So cost data for investment and energy consumption can easily and directly be compared.
 +\\
  
  
Line 64: Line 72:
 }}] }}]
 For the basic version of PH the costs for energy saving components are in total 322 €/m² TFA. This value is compatible with the experience from other projects.  For the basic version of PH the costs for energy saving components are in total 322 €/m² TFA. This value is compatible with the experience from other projects. 
 +\\
 Cost estimation for LEB. For this project no comparable LEB was available to get invoiced cost data. Therefore costs were estimated according to data from literature: less insulation thickness, no expenses for air-tightness, simple exhaust air ventilation system reduce the costs for the LEB. On the other hand the connection to district heating needs a higher maximum power (15 kW instead of 6 kW). The costs for the connection are rated directly with the maximum power. In addition the LEB has higher costs for heating system as each room has a radiator, whilst in PH one single air heater is used, radiators only in bathrooms.  Cost estimation for LEB. For this project no comparable LEB was available to get invoiced cost data. Therefore costs were estimated according to data from literature: less insulation thickness, no expenses for air-tightness, simple exhaust air ventilation system reduce the costs for the LEB. On the other hand the connection to district heating needs a higher maximum power (15 kW instead of 6 kW). The costs for the connection are rated directly with the maximum power. In addition the LEB has higher costs for heating system as each room has a radiator, whilst in PH one single air heater is used, radiators only in bathrooms. 
 +\\
 The sum of costs for energy saving components for the LEB are therefore only about 240 €/m² TFA and thus the difference to PH is 82 €/m². The relative extra expenses for PH components from these numbers are about 8 % which is in line with earlier PH projects. The sum of costs for energy saving components for the LEB are therefore only about 240 €/m² TFA and thus the difference to PH is 82 €/m². The relative extra expenses for PH components from these numbers are about 8 % which is in line with earlier PH projects.
 2.4 PH are economically reasonable,  2.4 PH are economically reasonable, 
Line 70: Line 80:
 PH components as described above are economically reasonable with present boundary conditions, see table 4. So the higher investment costs are paid back by reduced energy consumption costs during lifetime of the building. Therefore the documentation of 'total lifecycle costs' is important to give a transparent view of the facts. PH components as described above are economically reasonable with present boundary conditions, see table 4. So the higher investment costs are paid back by reduced energy consumption costs during lifetime of the building. Therefore the documentation of 'total lifecycle costs' is important to give a transparent view of the facts.
 Two effects have to be pointed out here:  Two effects have to be pointed out here: 
-  * Unordered List Itemit is worth while to optimize all components to the cost optimum. Having rather high energy prices this intends to reduce energy costs and have some more investments in corresponding energy saving components. +  * it is worth while to optimize all components to the cost optimum. Having rather high energy prices this intends to reduce energy costs and have some more investments in corresponding energy saving components. 
-  * Unordered List ItemThe numbers of cost data out of the study shown in this section are by intention taken from a 'cost effective' basic version of a building. This intends as well the selection of materials. So PVC window frames are used in PH and LEB. Extra costs for wooden or wood-aluminum are not accounted for. Using these would result in extra costs for both, PH an LEB. It is important to always compare apples with apples! + 
-  * Unordered List ItemWindows have cost reduction potential +  * The numbers of cost data out of the study shown in this section are by intention taken from a 'cost effective' basic version of a building. This intends as well the selection of materials. So PVC window frames are used in PH and LEB. Extra costs for wooden or wood-aluminum are not accounted for. Using these would result in extra costs for both, PH an LEB. It is important to always compare apples with apples! 
-  * Unordered List ItemVentilation systems have cost reduction potential.+ 
 +  * Windows have cost reduction potential 
 + 
 +  * Ventilation systems have cost reduction potential. 
 Using all the above mentioned numbers and calculating present values from all cost categories results in the total costs for PH and LEB shown in figure 3. Using all the above mentioned numbers and calculating present values from all cost categories results in the total costs for PH and LEB shown in figure 3.
 Summary and outlook: Lower interest rates get the capital cost reduced and higher energy prices will lead to higher savings. So the present situation favors investment in energy efficiency components for buildings. Summary and outlook: Lower interest rates get the capital cost reduced and higher energy prices will lead to higher savings. So the present situation favors investment in energy efficiency components for buildings.
Line 87: Line 101:
 | price for electricity *) | **0.22 €/kWh** | final energy|  | price for electricity *) | **0.22 €/kWh** | final energy| 
 **Table 2: ****Basic assumptions for dynamical cost calculation for row house 2008.  **Table 2: ****Basic assumptions for dynamical cost calculation for row house 2008. 
-Siehe dazu auch [Kah/Feist 2008]       (*) Energy price and interest rate in 2008.**+Also see [Kah/Feist 2008]       (*) Energy price and interest rate in 2008.**
  
 \\ \\
Line 114: Line 128:
 \\ \\
 **Conclusion**: it turns out clearly, that using **cost optimized but good quality PH components** which are to be developed consequently during the next few years, give potential to **realize cost effective 'deep energy renovation' projects**. Cost effective is said in this context with respect to total life cycle costs.  The same is true for **new built as well**.  **Conclusion**: it turns out clearly, that using **cost optimized but good quality PH components** which are to be developed consequently during the next few years, give potential to **realize cost effective 'deep energy renovation' projects**. Cost effective is said in this context with respect to total life cycle costs.  The same is true for **new built as well**. 
 +\\
 \\ \\
 This fact is crucial for so called contracting business models, which are to be developed within IEA Annex 61 [IEA61]: a contractor must be sure, that in the end the overall lifecycle cost – investment, energy, maintenance – will be as low as calculated before. If energy prices would increase, the risk of higher total costs will be higher for the 'low investment cost bundle'. So the concern of investors has to be redirected from the narrow view of pure short time investment costs to the wider view of total life cycle costs. This fact is crucial for so called contracting business models, which are to be developed within IEA Annex 61 [IEA61]: a contractor must be sure, that in the end the overall lifecycle cost – investment, energy, maintenance – will be as low as calculated before. If energy prices would increase, the risk of higher total costs will be higher for the 'low investment cost bundle'. So the concern of investors has to be redirected from the narrow view of pure short time investment costs to the wider view of total life cycle costs.
Line 120: Line 135:
  
  
- +[{{ :picopen:school_building_figure_6.png?700 |**Figure 6:** **School building – renovation with PH-components – variant No 6 was realized.   
-[{{ :picopen:school_building_renovation_with_ph-components_.png?nolink | **Figure 6:** **School building – renovation with PH-components – variant No 6 was realized.   +
 Detailed investment costs for energy saving actions in addition with basic 'anyway' needed costs, such as new rendering and new roof which are needed for any variant.**}}] Detailed investment costs for energy saving actions in addition with basic 'anyway' needed costs, such as new rendering and new roof which are needed for any variant.**}}]
 +
 \\ \\
-[{{ :picopen:school_building_renovation_with_ph-components_variant_no_6_was_realized..png?nolink | **Figure 7:** **School building – renovation with PH-components – variant No 6 was realized.  +[{{ :picopen:renovation_with_ph_comp.png?700 | **Figure 7:** **School building – renovation with PH-components – variant No 6 was realized.  
 Full life cycle costs as present cash value for 33 years. This time span is assumed as an average life time for all components.  Full life cycle costs as present cash value for 33 years. This time span is assumed as an average life time for all components. 
 The analysis shows clearly: the cost optimized variants No 5 (EnEV, german building code) and No 7 (PH) are equal within the accuracy of the calculations, see text.** The analysis shows clearly: the cost optimized variants No 5 (EnEV, german building code) and No 7 (PH) are equal within the accuracy of the calculations, see text.**
Line 151: Line 166:
 Acknowledgements: Part of this work was financed by German Government: Bundesministerium für Wirtschaft und Technologie (BMWi) in the framework of  Acknowledgements: Part of this work was financed by German Government: Bundesministerium für Wirtschaft und Technologie (BMWi) in the framework of 
   * IEA Task37 "Advanced Housing Renovation with Solar & Conservation" and in the framework of    * IEA Task37 "Advanced Housing Renovation with Solar & Conservation" and in the framework of 
 +
   * IEA Annex 61 "Business and Technical Concepts for Deep Energy Retrofits in Public Buildings"  and by    * IEA Annex 61 "Business and Technical Concepts for Deep Energy Retrofits in Public Buildings"  and by 
 +
   * Deutsche Bundesstiftung Umwelt  and supporters  of "Arbeitskreis Kostengünstige Passivhäuser, V" [AKKP42].   * Deutsche Bundesstiftung Umwelt  and supporters  of "Arbeitskreis Kostengünstige Passivhäuser, V" [AKKP42].
 +
 +
 +
 +\\ \\ \\ \\ \\
 +|//The sole responsibility for the content of Passipedia lies with the authors. \\ While certain marked articles have been created with the support of the EU, they do not necessarily reflect the opinion of the European Union; \\ Neither the EACI nor the European Commission are responsible for any use that may be made of the information contained therein.//| \\
 +\\
 +
  
basics/affordability/economic_feasibility_of_passive_house_design.1435740277.txt.gz · Last modified: 2015/07/01 10:44 by kdreimane