planning:thermal_protection:thermal_protection_works:comparison_of_in_situ_measurements_and_hygrothermal_simulations_of_four_different_interior_insulation_systems:start
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revision | |||
planning:thermal_protection:thermal_protection_works:comparison_of_in_situ_measurements_and_hygrothermal_simulations_of_four_different_interior_insulation_systems:start [2014/09/18 18:19] – external edit 127.0.0.1 | planning:thermal_protection:thermal_protection_works:comparison_of_in_situ_measurements_and_hygrothermal_simulations_of_four_different_interior_insulation_systems:start [2019/10/14 09:35] (current) – [Conclusions] cblagojevic | ||
---|---|---|---|
Line 35: | Line 35: | ||
* Indoor conditions are at least as important as the insulation system itself for the moisture level within the construction. | * Indoor conditions are at least as important as the insulation system itself for the moisture level within the construction. | ||
+ | |||
* Especially in the context of interior insulation an air ventilation unit helps to limit the indoor RH and is necessary to achieve low humidity within the construction. \\ | * Especially in the context of interior insulation an air ventilation unit helps to limit the indoor RH and is necessary to achieve low humidity within the construction. \\ | ||
\\ | \\ |
planning/thermal_protection/thermal_protection_works/comparison_of_in_situ_measurements_and_hygrothermal_simulations_of_four_different_interior_insulation_systems/start.txt · Last modified: 2019/10/14 09:35 by cblagojevic