User Tools

Site Tools


sinfonia:energy_efficiency_in_domestic_electrical_energy_use

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
Next revisionBoth sides next revision
sinfonia:energy_efficiency_in_domestic_electrical_energy_use [2020/06/26 17:42] – [Sources] gergina.radeva@passiv.desinfonia:energy_efficiency_in_domestic_electrical_energy_use [2020/07/14 16:59] – [Results] gergina.radeva@passiv.de
Line 77: Line 77:
 The floor area of the apartments averages to 67 m², a typical size for apartments of the era of construction. \\ The floor area of the apartments averages to 67 m², a typical size for apartments of the era of construction. \\
  
-[{{:picopen:number_of_households_per_number_of_occupants.png?400 |Figure 2.: Number of households per number of occupants}}] [{{:picopen:floor_area_of_apartments.png?400|Figure 3.: Floor area of apartments, in ascending order}}] \\+[{{:picopen:number_of_households_per_number_of_occupants.png?700 |Figure 2.: Number of households per number of occupants}}] [{{:picopen:floor_area_of_apartments.png?700|Figure 3.: Floor area of apartments, in ascending order}}] \\
  
 \\ \\
Line 87: Line 87:
 ==== Per Household ==== ==== Per Household ====
  
-[{{:picopen:total_annual_electricity_use_of_households.png?400|Figure 4.: Total annual electricity use of households, in ascending order, as found}}]+[{{:picopen:total_annual_electricity_use_of_households.png?700|Figure 4.: Total annual electricity use of households, in ascending order, as found}}]
  
-[{{:picopen:total_annual_electricity_use_of_households_optimised.png?400|Figure 5.: Total annual electricity use of households, in ascending order, optimised}}]+[{{:picopen:total_annual_electricity_use_of_households_optimised.png?700|Figure 5.: Total annual electricity use of households, in ascending order, optimised}}]  \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
  
 As can be seen in Fig. 4 the electricity usage is spread over a wide range, with a factor of about 8 between the smallest and the largest value. In this it resembles the variability of domestic hot water usage. The data were not formally probed for random distribution but do not suggest a deviation from a normal distribution either. The mean value is hence considered a useful representation of the total sample, it amounts to 2715 kWh/a per household. \\ As can be seen in Fig. 4 the electricity usage is spread over a wide range, with a factor of about 8 between the smallest and the largest value. In this it resembles the variability of domestic hot water usage. The data were not formally probed for random distribution but do not suggest a deviation from a normal distribution either. The mean value is hence considered a useful representation of the total sample, it amounts to 2715 kWh/a per household. \\
Line 99: Line 99:
 A rating system developed by [ISOE] was applied to group the households into energy efficiency classes. It allows for DHW (domestic hot water)-preparation based on electricity or not as well as for the number of persons and the fact whether the unit is a flat or house. \\ A rating system developed by [ISOE] was applied to group the households into energy efficiency classes. It allows for DHW (domestic hot water)-preparation based on electricity or not as well as for the number of persons and the fact whether the unit is a flat or house. \\
  
-[{{:picopen:energy_efficiency_classes_of_households_as_found.png?400|Figure 6.: energy efficiency classes of households, as found}}] +[{{:picopen:energy_efficiency_classes_of_households_as_found.png?700|Figure 6.: Energy efficiency classes of households, as found}}] 
  
-[{{:picopen:energy_efficiency_classes_of_households_optimised.png?400|Figure 7.: energy efficiency classes of households, optimised}}] In the existing condition the average rating is 4.35 out of 7. The highest ratings occur for very small households with high electricity use as well as for 4-person households. Given the not representative composition of the sample of households under consideration no systematic correlations can be studied. \\+[{{:picopen:energy_efficiency_classes_of_households_optimised.png?700|Figure 7.: Energy efficiency classes of households, optimised}}] \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ 
 + 
 +In the existing condition the average rating is 4.35 out of 7. The highest ratings occur for very small households with high electricity use as well as for 4-person households. Given the not representative composition of the sample of households under consideration no systematic correlations can be studied. \\
  
 If the improvements described above are made, the household classification averages to 2.9, a considerable improvement. However, in some households very high consumption still prevails. While the relative order of the highest-consuming households does not change in most of the cases, in one instance a drop from 6 to 3 rating can be observed, based on the replacement of a very poor deep freezer in a single person household. \\ If the improvements described above are made, the household classification averages to 2.9, a considerable improvement. However, in some households very high consumption still prevails. While the relative order of the highest-consuming households does not change in most of the cases, in one instance a drop from 6 to 3 rating can be observed, based on the replacement of a very poor deep freezer in a single person household. \\
Line 109: Line 111:
 On a per-capita basis the electricity use amounts to 1777 kWh/(p a) on average. The spread is considerable with a factor of ca. 2.5 for min and max relative to the mean. \\ On a per-capita basis the electricity use amounts to 1777 kWh/(p a) on average. The spread is considerable with a factor of ca. 2.5 for min and max relative to the mean. \\
  
-[{{:picopen:person_specific_electricity_use_as_found.png?400|Figure 8.: Person specific electricity use, as found}}]  [{{:picopen:person_specific_electricity_use_optimised.png?400|Figure 9.: Person specific electricity use, optimised}}]+[{{:picopen:person_specific_electricity_use_as_found.png?700|Figure 8.: Person specific electricity use, as found}}]  [{{:picopen:person_specific_electricity_use_optimised.png?700|Figure 9.: Person specific electricity use, optimised}}]
  
 + \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
 With low hanging fruits reaped the mean is lowered to 1432 kWh/(p a) while the spread rather increases. Particularly the highest-consuming households appear to respond less to such measures.  \\ With low hanging fruits reaped the mean is lowered to 1432 kWh/(p a) while the spread rather increases. Particularly the highest-consuming households appear to respond less to such measures.  \\
  
Line 121: Line 124:
 For newly build Passive House buildings with all-recent appliances of reasonable energy efficiency and typically also larger TFA values of 20 kWh/(m²a) and below are typical. Accounting for the smaller size of the apartments present in this study (65 m²) but with a similar inventory of appliances values around 23 kWh/(m²a) would be expected according to [PHPP]. This in comparison to the measured mean value of 43 kWh/(m²a) suggests a considerable potential for improvements. \\ For newly build Passive House buildings with all-recent appliances of reasonable energy efficiency and typically also larger TFA values of 20 kWh/(m²a) and below are typical. Accounting for the smaller size of the apartments present in this study (65 m²) but with a similar inventory of appliances values around 23 kWh/(m²a) would be expected according to [PHPP]. This in comparison to the measured mean value of 43 kWh/(m²a) suggests a considerable potential for improvements. \\
  
-[{{:picopen:area_specific_electricity_use_as_found.png?400|Figure 10.: area specific electricity use, as found}}] [{{:picopen:area_specific_electricity_use_optimised.png?400|Figure 11.: area specific electricity use, optimised}}] +[{{:picopen:area_specific_electricity_use_as_found.png?700|Figure 10.: area specific electricity use, as found}}] [{{:picopen:area_specific_electricity_use_optimised.png?700|Figure 11.: area specific electricity use, optimised}}] 
 +\\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
 In the scenario with low hanging fruits reaped about half of the potential estimated before is incurred. It might be even more, as the usage of some sorts of equipment, in particular the use of TV/entertainment has shown to be much more intense than in the standard assumptions of [PHPP] as will be studied in the following chapter. \\ In the scenario with low hanging fruits reaped about half of the potential estimated before is incurred. It might be even more, as the usage of some sorts of equipment, in particular the use of TV/entertainment has shown to be much more intense than in the standard assumptions of [PHPP] as will be studied in the following chapter. \\
  
Line 136: Line 139:
  
 ==== Sectors ==== ==== Sectors ====
-[{{:picopen:appliance_categories_and_respective_number_of_samples.png?400|Figure 12.: Appliance Categories and respective number of samples}}] +[{{:picopen:appliance_categories_and_respective_number_of_samples.png?700|Figure 12.: Appliance Categories and respective number of samples}}] 
-[{{:picopen:mean_annual_consumption_per_appliance_category.png?400|Figure 13.: Mean Annual Consumption per Appliance Category, Min and Max Values. Where available an approximate A+++ figure for standard labelled consumption is supplemented as a triangular mark (ecotopten)}}] +[{{:picopen:mean_annual_consumption_per_appliance_category.png?700|Figure 13.: Mean Annual Consumption per Appliance Category, Min and Max Values. Where available an approximate A+++ figure for standard labelled consumption is supplemented as a triangular mark (ecotopten)}}] 
 +\\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
 While many more specific items were measured, a useful evaluation can be performed on the major categories of household appliances as given in Fig. 11 above. \\ While many more specific items were measured, a useful evaluation can be performed on the major categories of household appliances as given in Fig. 11 above. \\
  
Line 151: Line 154:
 ==== Share of the Sectorial Electrical Energy Use in the Total ==== ==== Share of the Sectorial Electrical Energy Use in the Total ====
  
-[{{:picopen:share_of_mean_consumption_per_appliance_category_in_total_annual_consumption.png?400|Figure 14.: Share of Mean Consumption per Appliance Category in Total Annual Consumption. Highlighted is the “refrigeration” group of categories}}]+[{{:picopen:share_of_mean_consumption_per_appliance_category_in_total_annual_consumption.png?700|Figure 14.: Share of Mean Consumption per Appliance Category in Total Annual Consumption. Highlighted is the “refrigeration” group of categories}}]
  
 Refrigeration appliances lead also the relative consumption, particularly as two of the listed categories are sometimes present in the same household. Reportedly many appliances were “12-15 years old” and no energy label was available for any of them. Interestingly entertainment/TV comes in second overall, while in some specific households it is even the dominant consumption category. Washing/Drying/Telecommunication each contribute in the range of 5 %.  \\ Refrigeration appliances lead also the relative consumption, particularly as two of the listed categories are sometimes present in the same household. Reportedly many appliances were “12-15 years old” and no energy label was available for any of them. Interestingly entertainment/TV comes in second overall, while in some specific households it is even the dominant consumption category. Washing/Drying/Telecommunication each contribute in the range of 5 %.  \\
Line 164: Line 167:
  
 This comparison is mainly an excerpt from a Bachelor thesis by T. Molitor, UIBK, which was compiled along the work on the SINFONIA project. It is enlightening to put the results from the monitoring campaign in Innsbruck into a larger perspective and compare them to national averages from Austria and other European countries. This comparison is mainly an excerpt from a Bachelor thesis by T. Molitor, UIBK, which was compiled along the work on the SINFONIA project. It is enlightening to put the results from the monitoring campaign in Innsbruck into a larger perspective and compare them to national averages from Austria and other European countries.
-[{{:picopen:annual_total_electricity_consumption_in_austria_compared_to_germany_and_uk.png?400|Figure 15.: Annual total Electricity Consumption in Austria compared to Germany and UK}}]+[{{:picopen:annual_total_electricity_consumption_in_austria_compared_to_germany_and_uk.png?700|Figure 15.: Annual total Electricity Consumption in Austria compared to Germany and UK}}]
  
 The monitoring yielded an average annual electricity consumption of 2715 kWh, the majority of samples being taken from one and two person households (cf. Fig. 1). This is a little higher than the national figures in Fig. 14 would suggest. One reason might be the higher than average age of the tenants in the sample with their older than average stock of appliances (Fig. 12). \\ The monitoring yielded an average annual electricity consumption of 2715 kWh, the majority of samples being taken from one and two person households (cf. Fig. 1). This is a little higher than the national figures in Fig. 14 would suggest. One reason might be the higher than average age of the tenants in the sample with their older than average stock of appliances (Fig. 12). \\
Line 170: Line 173:
 Statistical surveys available for various countries and the EU average are hampered by the fact that Austria applies a different set of categories to group the shares. Given the very similar total amounts for Austria and Germany in Fig. 14 and generally similar preferences it may not miss the reality much if the German shares are compared instead. \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ Statistical surveys available for various countries and the EU average are hampered by the fact that Austria applies a different set of categories to group the shares. Given the very similar total amounts for Austria and Germany in Fig. 14 and generally similar preferences it may not miss the reality much if the German shares are compared instead. \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
  
- +\\ \\ \\ \\ \\ \\ \\ \\ 
-{{:picopen:annual_share_in_total_consumption_austria.png?180|}} {{:picopen:annual_share_in_total_consumption_germany.png?180|}}{{:picopen:annual_share_in_total_consumption_united_kingdom.png?180|}}{{:picopen:annual_share_in_total_consumption_sweden.png?180|}} {{:picopen:annual_share_in_total_consumption_europe.png?180|}} \\+{{:picopen:annual_share_in_total_consumption_austria.png?400|}} {{:picopen:annual_share_in_total_consumption_germany.png?400|}}{{:picopen:annual_share_in_total_consumption_united_kingdom.png?400|}}{{:picopen:annual_share_in_total_consumption_sweden.png?400|}} {{:picopen:annual_share_in_total_consumption_europe.png?420|}} \\
  
  Figure 16.: Annual Share per Category in Different Countries \\  Figure 16.: Annual Share per Category in Different Countries \\
Line 196: Line 199:
 Three examples were assessed, with one sample each for the A+, A++ and A+++ rating respectively. The A+++ rated fridge/freezer was further studied with various temperature settings for fridge and freezer. All appliances were in regular use in households at the time of measurement. \\ Three examples were assessed, with one sample each for the A+, A++ and A+++ rating respectively. The A+++ rated fridge/freezer was further studied with various temperature settings for fridge and freezer. All appliances were in regular use in households at the time of measurement. \\
  
-[{{:picopen:comparison_of_measured_annual_energy_consumption.png?400|Figure 17.: Comparison of Measured Annual Energy Consumption and Energy Label Standard Demand Figures for three Appliances and Numerous Temperature Settings in one Instance.}}]+[{{:picopen:comparison_of_measured_annual_energy_consumption.png?700|Figure 17.: Comparison of Measured Annual Energy Consumption and Energy Label Standard Demand Figures for three Appliances and Numerous Temperature Settings in one Instance.}}]
  
 This limited sample of appliances is, of course, not statistically significant. The results suggest, however, that the standard energy consumption figures from energy labels can indeed be used to make a reasonable estimate of the actual in-situ performance. It appears that the figures are even on the conservative side for all but the most extreme temperature settings. With extreme temperature settings the actual consumption rose by 20 % above the standard consumption as labelled. With economic temperature settings the studied unit outperformed the labelled standard consumption by a good 25 %. During vacations, when the door remains shut, the consumption decreases further. This effect contributes to the conservative estimate as such periods happen in most households. \\ This limited sample of appliances is, of course, not statistically significant. The results suggest, however, that the standard energy consumption figures from energy labels can indeed be used to make a reasonable estimate of the actual in-situ performance. It appears that the figures are even on the conservative side for all but the most extreme temperature settings. With extreme temperature settings the actual consumption rose by 20 % above the standard consumption as labelled. With economic temperature settings the studied unit outperformed the labelled standard consumption by a good 25 %. During vacations, when the door remains shut, the consumption decreases further. This effect contributes to the conservative estimate as such periods happen in most households. \\
Line 210: Line 213:
 In order to do a target-oriented consultation to reduce the energy consumption of households, a tool was developed that allows the listing of all household appliances individually with their power and energy consumptions per usage. Besides the energy-related parameters, the recording of frequency and duration of usage is equally important, as only with the knowledge of power input AND usage the consumption per year can be estimated.  In order to do a target-oriented consultation to reduce the energy consumption of households, a tool was developed that allows the listing of all household appliances individually with their power and energy consumptions per usage. Besides the energy-related parameters, the recording of frequency and duration of usage is equally important, as only with the knowledge of power input AND usage the consumption per year can be estimated. 
  
-[{{ :picopen:section_of_the_energy_efficienca_tool.png?400|Figure 18.: Section from the Energy Efficiency Tool to list all energy consumer individually. Here you can see the input area for white ware including frequency of usage, recommended alternatives and savings per year.}}] +[{{ :picopen:section_of_the_energy_efficienca_tool.png?700|Figure 18.: Section from the Energy Efficiency Tool to list all energy consumer individually. Here you can see the input area for white ware including frequency of usage, recommended alternatives and savings per year.}}] 
 A general assumption for the usage could lead to strayed optimisations in many cases. This applies especially for white ware such as refrigeration appliances, dish washers, washing machines and tumble driers. Depending on the frequency of usage, which e. g. for the tumble dryer can vary between a few times per month to up to several times per day, investing in a new appliance can be absolutely not recommendable or highly profitable. Furthermore the usage and standby periods are recorded and the energy consumption for lighting can be taken into consideration. \\ A general assumption for the usage could lead to strayed optimisations in many cases. This applies especially for white ware such as refrigeration appliances, dish washers, washing machines and tumble driers. Depending on the frequency of usage, which e. g. for the tumble dryer can vary between a few times per month to up to several times per day, investing in a new appliance can be absolutely not recommendable or highly profitable. Furthermore the usage and standby periods are recorded and the energy consumption for lighting can be taken into consideration. \\
  
 The total energy consumption per year has turned out to be an important benchmark for making sure all relevant appliances have been listed. Previous experience has shown good correlation of the overall consumption and the calculated prognosis with a typical deviation of less than 15 %. In addition to the presently used appliances alternatives can be entered and savings can be calculated accordingly. The total energy consumption per year has turned out to be an important benchmark for making sure all relevant appliances have been listed. Previous experience has shown good correlation of the overall consumption and the calculated prognosis with a typical deviation of less than 15 %. In addition to the presently used appliances alternatives can be entered and savings can be calculated accordingly.
 +\\ \\ \\ 
 === Monitoring of the Electric Energy Consumption === === Monitoring of the Electric Energy Consumption ===
  
 In addition to the energy consumption the user profiles can be determined from the monitoring results. The following figure shows the measured energy consumption of individual appliances in one exemplary household. In combination with the information from the consultation tool this results in a potential overall reduction of 30 %.  In addition to the energy consumption the user profiles can be determined from the monitoring results. The following figure shows the measured energy consumption of individual appliances in one exemplary household. In combination with the information from the consultation tool this results in a potential overall reduction of 30 %. 
  
-[{{ :picopen:measured_consumption_curves.jpg?400|Figure 19.: Overview over measured consumption curves of various consumers in a household (left). Next to it the current energy consumption and the expected consumption after all recommended measures form the consultation put into action with an overall reduction of 30 % (right).}}]+[{{ :picopen:measured_consumption_curves.jpg?700|Figure 19.: Overview over measured consumption curves of various consumers in a household (left). Next to it the current energy consumption and the expected consumption after all recommended measures form the consultation put into action with an overall reduction of 30 % (right).}}]
  
 Based on the available data an economic evaluation of the viability of optimisations was performed. The assessment was based on a life cycle cost approach. Finally the household electrical energy efficiency class rating for actual and optimised configuration are also shown. \\ Based on the available data an economic evaluation of the viability of optimisations was performed. The assessment was based on a life cycle cost approach. Finally the household electrical energy efficiency class rating for actual and optimised configuration are also shown. \\
Line 225: Line 228:
 **All results and recommendations thus obtained are wrapped up on a results sheet and explained to the participants comprehensively and in person. This is considered a very important factor for the success of the approach as it builds confidence as well as understanding.** \\ **All results and recommendations thus obtained are wrapped up on a results sheet and explained to the participants comprehensively and in person. This is considered a very important factor for the success of the approach as it builds confidence as well as understanding.** \\
  
-[{{:picopen:energy_consulting_results_sheet.png?400|Figure 20.: Energy consulting results sheet comparing actual and optimised electricity use, the saving potential, pointing out recommended improvements and their economic benefit}}]+[{{:picopen:energy_consulting_results_sheet.png?500|Figure 20.: Energy consulting results sheet comparing actual and optimised electricity use, the saving potential, pointing out recommended improvements and their economic benefit}}]
  
 ===== Experiments with Real-Time Feedback on Energy Use to the Tenants ===== ===== Experiments with Real-Time Feedback on Energy Use to the Tenants =====
Line 249: Line 252:
 === Sample 01 === === Sample 01 ===
  
-[{{ :picopen:sample_01.png?400|Figure 21.: Sample 01, overview of metered consumption, linearised for the experiment phases}}] [{{ :picopen:gradients_of_all_experiment_phase.jpg?400|Table 2: Gradients for all experiment phases, average kWh per day}}]+[{{ :picopen:sample_01.png?700|Figure 21.: Sample 01, overview of metered consumption, linearised for the experiment phases}}] [{{ :picopen:gradients_of_all_experiment_phase.jpg?700|Table 2: Gradients for all experiment phases, average kWh per day}}]
 Data sample 01 was acquired in a three-person household within a multifamily building, domestic hot water was prepared with an electric resistance heater. Coincidentally, data acquisition ended on the date when the CoVID19-related lockdown commenced. \\ Data sample 01 was acquired in a three-person household within a multifamily building, domestic hot water was prepared with an electric resistance heater. Coincidentally, data acquisition ended on the date when the CoVID19-related lockdown commenced. \\
  
Line 258: Line 261:
 === Sample 02 === === Sample 02 ===
  
- [{{ :picopen:sample_02.png?400|Figure 22.: Sample 02, overview of metered consumption, linearised for the experiment phases}}]  [{{ :picopen:gradients_of_all_experiment_phase_2.jpg?400|Table 3: Gradients for all experiment phases, average kWh per day}}]+ [{{ :picopen:sample_02.png?700|Figure 22.: Sample 02, overview of metered consumption, linearised for the experiment phases}}]  [{{ :picopen:gradients_of_all_experiment_phase_2.jpg?700|Table 3: Gradients for all experiment phases, average kWh per day}}]
 Data sample 02 was acquired in a three-person household within a multifamily building, domestic hot water is prepared with a gas boiler. Coincidentally, data acquisition ended on the date when the CoVID19-related lockdown commenced. \\ Data sample 02 was acquired in a three-person household within a multifamily building, domestic hot water is prepared with a gas boiler. Coincidentally, data acquisition ended on the date when the CoVID19-related lockdown commenced. \\
  
 The total consumption in the time of the experiment amounted to a good 600 kWh in sample 02, which extrapolates to around 2400 kWh per annum. This is a household with very low energy consumption, without electrical DHW preparation. \\ The total consumption in the time of the experiment amounted to a good 600 kWh in sample 02, which extrapolates to around 2400 kWh per annum. This is a household with very low energy consumption, without electrical DHW preparation. \\
  
-It is obvious from the gradients given in table 3 that feeding back information on the energy consumption had no reduction effect in the case of sample 02. On the contrary, the average daily consumption has slightly increased within the feedback phase. However it decreased again in phase 3 and the variation was minimal. Essentially the energy use has been unaffected by the changing boundary conditions of the different experimental phases, despite the advent of spring.  \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\+It is obvious from the gradients given in table 3 that feeding back information on the energy consumption had no reduction effect in the case of sample 02. On the contrary, the average daily consumption has slightly increased within the feedback phase. However it decreased again in phase 3 and the variation was minimal. Essentially the energy use has been unaffected by the changing boundary conditions of the different experimental phases, despite the advent of spring.  \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
  
  
 === Sample 03 === === Sample 03 ===
-[{{ :picopen:sample_03.png?400|Figure 23.: Sample 03, overview of metered consumption, linearised for the experiment phases}}] [{{ :picopen:gradients_of_all_experiment_phase_3.jpg?400|Table 4: Gradients for all experiment phases, average kWh per day}}]+[{{ :picopen:sample_03.png?700|Figure 23.: Sample 03, overview of metered consumption, linearised for the experiment phases}}] [{{ :picopen:gradients_of_all_experiment_phase_3.jpg?700|Table 4: Gradients for all experiment phases, average kWh per day}}]
  
 Data sample 03 was acquired in a three-person household within a multifamily building, domestic hot water is prepared with a gas boiler. Data acquisition continued for about 10 days onto the period of the CoVID19-related lockdown. \\ Data sample 03 was acquired in a three-person household within a multifamily building, domestic hot water is prepared with a gas boiler. Data acquisition continued for about 10 days onto the period of the CoVID19-related lockdown. \\
Line 273: Line 276:
 The total consumption in the time of the experiment amounted to a good 3000 kWh in sample 03, which extrapolates to around 10000 kWh per annum. This is a household with extremely high energy consumption, without electrical DHW preparation included in the data. \\ The total consumption in the time of the experiment amounted to a good 3000 kWh in sample 03, which extrapolates to around 10000 kWh per annum. This is a household with extremely high energy consumption, without electrical DHW preparation included in the data. \\
  
-It is obvious from the gradients given in table 4 that feeding back information on the energy consumption had a persistent reduction effect in the case of sample 03. It held into phase 3, however, a slight reduction in energy consumption might also be attributed to the advent of spring and changed habits due to the CoVID19-related lockdown. \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\+It is obvious from the gradients given in table 4 that feeding back information on the energy consumption had a persistent reduction effect in the case of sample 03. It held into phase 3, however, a slight reduction in energy consumption might also be attributed to the advent of spring and changed habits due to the CoVID19-related lockdown. \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
  
  
-=== Sample 04 === 
-[{{ :picopen:sample_04.png?400|Figure 24.: Sample 04, overview of metered consumption, linearised for the experiment phases}}] [{{ :picopen:gradients_of_all_experiment_phase_4.jpg?400|Table 5: Gradients for all experiment phases}}] 
  
 +
 +[{{ :picopen:sample_04.png?700|Figure 24.: Sample 04, overview of metered consumption, linearised for the experiment phases}}] [{{ :picopen:gradients_of_all_experiment_phase_4.jpg?700|Table 5: Gradients for all experiment phases}}]
 +\\ \\ \\ \\ \\ \\ \\ \\ \\
 +=== Sample 04 ===
 Data sample 04 was acquired in a two-person household within a multifamily building, domestic hot water preparation was electric but metered separately and is thus not part of the shown data. Data acquisition continued for about five weeks onto the period of the CoVID19-related lockdown. \\ Data sample 04 was acquired in a two-person household within a multifamily building, domestic hot water preparation was electric but metered separately and is thus not part of the shown data. Data acquisition continued for about five weeks onto the period of the CoVID19-related lockdown. \\
  
 The total consumption in the time of the experiment amounted to a good 1600 kWh in sample 04, which extrapolates to around 6500 kWh per annum. This is another household with extremely high energy consumption, without electrical DHW preparation included in the data. \\ The total consumption in the time of the experiment amounted to a good 1600 kWh in sample 04, which extrapolates to around 6500 kWh per annum. This is another household with extremely high energy consumption, without electrical DHW preparation included in the data. \\
  
-It is obvious from the gradients given in table 5 that feeding back information on the energy consumption had a slight reduction effect in the case of sample 04. It held into phase 3, however, a slight reduction in energy consumption might also be attributed to the advent of spring and changed habits due to the CoVID19-related lockdown. Since the latter covered a substantial part of the experiment’s time added uncertainty must be assumed as to the effect of changed habits. \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\+It is obvious from the gradients given in table 5 that feeding back information on the energy consumption had a slight reduction effect in the case of sample 04. It held into phase 3, however, a slight reduction in energy consumption might also be attributed to the advent of spring and changed habits due to the CoVID19-related lockdown. Since the latter covered a substantial part of the experiment’s time added uncertainty must be assumed as to the effect of changed habits. \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
  
 === Daytime Energy Use Incentives Phase === === Daytime Energy Use Incentives Phase ===
  
-[{{ :picopen:average_hourly_load_curve.png?400|Figure 25.: Average Hourly Load Curve for Households according to [Zimmermann_2012]}}]+[{{ :picopen:average_hourly_load_curve.png?700|Figure 25.: Average Hourly Load Curve for Households according to [Zimmermann_2012]}}]
 According to the literature, the usual temporal distribution of electricity use as observed in the field is not optimally aligned with the PV generation characteristics and peaks in the early morning and, particularly, in the evening hours (cf. figure, exemplary taken from [Zimmermann_2012]). \\ According to the literature, the usual temporal distribution of electricity use as observed in the field is not optimally aligned with the PV generation characteristics and peaks in the early morning and, particularly, in the evening hours (cf. figure, exemplary taken from [Zimmermann_2012]). \\
  
Line 294: Line 299:
 The typical daily load curve for households is well known from various studies. The above figure illustrates this with a chart from [Zimmermann_2012]. During the small hours of the night the load is low, with a steep increase in the morning when people get up and start their daily routine. After this rush hour a slight decrease and a minor peak around lunch time can be observed. The main activities only begin after four in the afternoon when inhabitants return home, cook meals, and start electronic entertainment equipment. \\ The typical daily load curve for households is well known from various studies. The above figure illustrates this with a chart from [Zimmermann_2012]. During the small hours of the night the load is low, with a steep increase in the morning when people get up and start their daily routine. After this rush hour a slight decrease and a minor peak around lunch time can be observed. The main activities only begin after four in the afternoon when inhabitants return home, cook meals, and start electronic entertainment equipment. \\
  
-Five data logging systems were deployed in late 2019/early 2020 of which three provided data with sufficient quality for hourly evaluation. \\ \\ \\ \\ \\+Five data logging systems were deployed in late 2019/early 2020 of which three provided data with sufficient quality for hourly evaluation. 
  
-[{{:picopen:sample_01_feedback.png?400|Figure 26.: Sample 01, Load curve for Feedback Phase of Experiment. Boxplot with Quartiles.}}] [{{:picopen:sample_01_special_tariff.png?400|Figure 27.: Sample 01, Load curve for Special Tariff  Phase of Experiment. Boxplot with Quartiles.}}]+ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ 
 +[{{:picopen:sample_01_feedback.png?500|Figure 26.: Sample 01, Load curve for Feedback Phase of Experiment. Boxplot with Quartiles.}}] [{{:picopen:sample_01_special_tariff.png?500|Figure 27.: Sample 01, Load curve for Special Tariff  Phase of Experiment. Boxplot with Quartiles.}}]
  
 In sample 01 it seems that the variability of electricity use differed somewhat in the two consecutive experiment phases but the general pattern of the median hourly share in the daily total appears to exhibit no significant change. The median curve largely follows the characteristics determined by other studies, e.g. [Zimmermann_2012]. There is no indication that daytime energy use had been incentivised in a significant way by the daytime price. \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ In sample 01 it seems that the variability of electricity use differed somewhat in the two consecutive experiment phases but the general pattern of the median hourly share in the daily total appears to exhibit no significant change. The median curve largely follows the characteristics determined by other studies, e.g. [Zimmermann_2012]. There is no indication that daytime energy use had been incentivised in a significant way by the daytime price. \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\
  
-[{{:picopen:sample_02_feedback.png?400|Figure 28.: Sample 02, Load curve for Feedback Phase of Experiment. Boxplot with Quartiles.}}] +\\ \\ 
-[{{:picopen:sample_02_special_tariff.png?400|Figure 29.: Sample 02, Load curve for Special Tariff  Phase of Experiment. Boxplot with Quartiles.}}]+[{{:picopen:sample_02_feedback.png?500|Figure 28.: Sample 02, Load curve for Feedback Phase of Experiment. Boxplot with Quartiles.}}] 
 +[{{:picopen:sample_02_special_tariff.png?500|Figure 29.: Sample 02, Load curve for Special Tariff  Phase of Experiment. Boxplot with Quartiles.}}]
 In sample 02 it seems that the variability of electricity use is pronounced in this household and differed less than in sample 01 in the two consecutive experiment phases. The general pattern of the median hourly share in the daily total, however, still follows the average profile rather well. One notable difference, for both phases of the experiment is, that in this household the morning hump is more pronounced than the evening hump. If a change in user behaviour can be observed it is a shift of the energy use towards the evening but there are no signs for increased daytime energy use. In sample 02 it seems that the variability of electricity use is pronounced in this household and differed less than in sample 01 in the two consecutive experiment phases. The general pattern of the median hourly share in the daily total, however, still follows the average profile rather well. One notable difference, for both phases of the experiment is, that in this household the morning hump is more pronounced than the evening hump. If a change in user behaviour can be observed it is a shift of the energy use towards the evening but there are no signs for increased daytime energy use.
  
- \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ + \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ \\ 
-[{{:picopen:sample_03_feedback.png?400|Figure 30.: Sample 03, Load curve for Feedback Phase of Experiment. Boxplot with Quartiles}}] +[{{:picopen:sample_03_feedback.png?500|Figure 30.: Sample 03, Load curve for Feedback Phase of Experiment. Boxplot with Quartiles}}] 
-[{{:picopen:sample_03_special_tariff.png?400|Figure 31.: Sample 03, Load curve for Special Tariff  Phase of Experiment. Boxplot with Quartiles.}}]+[{{:picopen:sample_03_special_tariff.png?500|Figure 31.: Sample 03, Load curve for Special Tariff  Phase of Experiment. Boxplot with Quartiles.}}]
  
 In sample 03 both the variability of electricity use and the hourly share during the daytime hours seem to have increased from one phase of the experiment to the next. One notable difference to the average profile, for both phases of the experiment is, that in this household the morning hump is more pronounced than the evening hump. In this sample significant signs for increased daytime energy use can be observed. \\ In sample 03 both the variability of electricity use and the hourly share during the daytime hours seem to have increased from one phase of the experiment to the next. One notable difference to the average profile, for both phases of the experiment is, that in this household the morning hump is more pronounced than the evening hump. In this sample significant signs for increased daytime energy use can be observed. \\
Line 334: Line 341:
  
 In order to gain a better understanding of the potential for shifiting energy use to the high-yield times of PV sytems by special tariffs further investigation is required. However, the results of this study call for limited expectations. \\ In order to gain a better understanding of the potential for shifiting energy use to the high-yield times of PV sytems by special tariffs further investigation is required. However, the results of this study call for limited expectations. \\
 +
 +{{ :picopen:sinfonia_energy_efficiency_in_domestic_electrical_energy_use.pdf |SINFONIA_Energy Efficiency in Domestic Electrical Energy Use.pdf}}
  
 ===== Sources ===== ===== Sources =====
  
-BDEW, B. d.-u. Stromverbrauch im Haushalt. Berlin2016 +|BDEW, B. d.-u. Stromverbrauch im Haushalt. Berlin2016| 
-Dupret, M., Zimmermann, J., Schlomann, B., Gruber, E., Kofod, C., Feldberg, N., Vorizek, T. (2007)Residential Monitoring to Decrease Energy Use and Carbon Emissions in Europe. Coimbra. +|Dupret, M., Zimmermann, J., Schlomann, B., Gruber, E., Kofod, C., Feldberg, N., Vorizek, T. (2007)Residential Monitoring to Decrease Energy Use and Carbon Emissions in Europe. Coimbra.| 
-[ecotopten] www.ecotopten.de (march 2020) list of energy efficient appliances +|[ecotopten] www.ecotopten.de (march 2020) list of energy efficient appliances| 
-https://stromliste.at/nuetzliche-infos/durchschnittlicher-stromverbrauch. (20. 03 2018). +|https://stromliste.at/nuetzliche-infos/durchschnittlicher-stromverbrauch. (20. 03 2018).| 
-[FHEM] Freundliche Hausautomation und Energie Messung, online, https://fhem.de +|[FHEM] Freundliche Hausautomation und Energie Messung, online, https://fhem.de| 
-[ISOE] ISOE – Institut für sozial-ökologische Forschung (Projektkoordination)Stromeffizienzklassen für Haushalte. Förderung von Stromsparinnovationen in Haushalt, Markt und Gerätetechnik (Stromeffizienzklassen), onlinehttp://www.stromeffizienzklassen.de/uploads/media/Stromeffizienzklassen_Kurzfassung_20160621.pdf +|[ISOE] ISOE – Institut für sozial-ökologische Forschung (Projektkoordination) Stromeffizienzklassen für Haushalte. Förderung von Stromsparinnovationen in Haushalt, Markt und Gerätetechnik
-Pfluger, R., Wagner, W., Spörk-Dür, M., Kapferer, R., Braito, M., Ochs, F., & Suschek-Berger, J. (2012). Forschungsprojekt Passivhauswohnanlage Lodenareal. Gleisdorf: Energie Tirol. +|Stromeffizienzklassen online http://www.stromeffizienzklassen.de/uploads/media/Stromeffizienzklassen_Kurzfassung_20160621.pdf| 
-[PHPP] Passive House Planning Package PHPP v. 9.6a, Passive House Institute, Darmstadt 2016 +|Pfluger, R., Wagner, W., Spörk-Dür, M., Kapferer, R., Braito, M., Ochs, F., & Suschek-Berger, J. (2012).|Forschungsprojekt Passivhauswohnanlage Lodenareal. Gleisdorf: Energie Tirol.| 
-www.stromspiegel.de. (20. 03 2018). +|[PHPP] Passive House Planning Package PHPP v. 9.6a, Passive House Institute, Darmstadt 2016| 
-[Zimmermann 2009] Zimmermann, J. (2009). End-use metering campaign in 400 households in Sweden Assesment of the Potential Electricity Savings. Félines-sur-Rimandoule. +|www.stromspiegel.de. (20. 03 2018).| 
-[Zimmermann 2012] Zimmermann, J.-P., Ecans, M., Griggs, J., King, N., Harding, L., Roberts, P., & Evans, C. (2012). Household Electricity Survey. Oxford.+|[Zimmermann 2009] Zimmermann, J. (2009). End-use metering campaign in 400 households in Sweden Assesment of the Potential Electricity Savings. Félines-sur-Rimandoule.| 
 +|[Zimmermann 2012] Zimmermann, J.-P., Ecans, M., Griggs, J., King, N., Harding, L., Roberts, P., & Evans, C. (2012). Household Electricity Survey. Oxford.|
  
 ---- ----
Line 357: Line 367:
 \\ \\
 This project has received funding from the European Union’s Seventh Programme for research, technological development and demonstration under grant agreement No 609019.//  This project has received funding from the European Union’s Seventh Programme for research, technological development and demonstration under grant agreement No 609019.// 
- 
- 
- 
- 
- 
- 
- 
- 
- 
- 
- 
- 
- 
- 
  
  
  
    
sinfonia/energy_efficiency_in_domestic_electrical_energy_use.txt · Last modified: 2021/03/02 05:33 by naman.sukhija@passiv.de